Details
- Models of 1-pipe and 4-pipe types for different applications
- Standard: UL, ULC, FM, Vds, EN54-20 ...
- Flair smoke detection technology provides reliable early warning in many environments with reduced false alarm
- Multistage dust filters and optical protection with a clean air screen ensure effective smoke detection over the life of the head
- Four alarm levels and wide sensitivity range provide optimal protection for many applications
- LCD screen with intuitive icons provides instant information, convenient for instant processing.
- The intake error error thresholds for each throttle vary according to the air flow modes
- Smart filter retains dust and calculates the remaining life of the filter, convenient for pre-set maintenance time
- Extended event memory (20,000 events) for event analysis and system diagnostics
- SelfLearn smoke and flow mode (AutoLearn ™ smoke and flow)
- Reference feature to adapt to external environmental conditions to minimize false alarms
- Fully compatible with VLP and VESDAnet
- Remote monitoring with iVESDA for inspection and proactive maintenance
- Ethernet connection with Xtralis software for configuration, monitoring and maintenance
- Industry first. Aspirating detector secondary monitoring and maintenance via WiFi
- USB port for PC configuration and hardware upgrade using a memory stick
- Two programmable GPI connectors (1 for monitoring) for flexible remote control
- The spare parts can be replaced quickly and increase the maximum working time
Specs
- Supply voltage: 24 vdc normal (18-30 vdc)
- IP protection: IP40.
- Operating temperature: 0-39 degrees C (32-102 degrees F).
- Humidity: 5-95% RH, no dew.
- Minimum air flow for each pipe: 15 l / m
- Maximum coverage area: 1000-2000m2
- Pipe length: 100-280m
- Branch pipe length: 130-560m
- Event log: 20,000 events.